Send the specification and we will quote your flanges for data center cooling systems against it.
Flanges for data center cooling systems divide into eight working types, each holding a position in the chilled water, condenser water, facility water and technology cooling circuits.
Rajendra Flanges manufactures industrial steel flanges with large diameter flanges as our specialization, machined and inspected in house, each with an EN 10204 3.1 certificate.
Table Of Contents
A weld neck flange carries a tapered hub butt-welded to the pipe, transferring bending stress into the pipe wall instead of the weld root. That gives the best fatigue and thermal-cycling performance in the catalog, so main headers and pump discharge take weld neck flanges for chilled water, ordered to ASME B16.47 on campus mains.
One ordering point is missed often enough to be worth calling out. The bore is machined to a nominated pipe schedule, so that schedule belongs on the purchase order: a Class 150 NPS 12 weld neck bored for Sch 40 will not meet Sch 10S pipe.
The slip-on type slides over the pipe end and takes a double fillet weld. Fabrication is faster and cut length forgiving, so slip-on flanges for cooling water lines suit Class 150 runs, while headers with real thermal cycling stay on weld neck.
A blind flange is a bolted cap with no bore, and here it does something it does nowhere else. Open Compute Project guidance recommends preserving pipe paths and tap-off connection points to the facility water system, so liquid cooling can be added later. Blind flanges for capped tap-off points hold that provision open.
The flange in a lap joint assembly rotates freely on a welded stub end, and only the stub end touches the water. Bolt holes rotate into alignment during fit-up, and only the stub end has to be the specified alloy, so lap joint flanges and stub ends cut the alloy spend on long runs.
Small bore work uses socket weld flanges, published to NPS 3 (80 NB) under ASME B16.5, and threaded flanges, published to NPS 24 though rarely used above 50 NB. On cooling work both are kept to drains, vents and sensor tappings from 15 NB to 50 NB, and neither is suited to vibration. Ring and plate flanges are the waterworks forms used on large campus mains under AWWA C207 and C228.
A flange adaptor for grooved piping bolts a grooved pipe end to a flanged pump or chiller nozzle, so a grooved room meets flanged equipment without a transition spool.
Campus mains run past the size range of the standard most engineers reach for first. ASME B16.47 large diameter flanges cover NPS 26 through NPS 60 in Classes 75 to 900. Series A descends from MSS SP-44 and Series B from API 605, and the two do not bolt together. Series A is heavier and thicker at the same size and class, with a larger bolt circle and different bolting. Bolt count, bolt size and bolt circle are fixed per series, class and size in the B16.47 tables, and they differ between the two series. Confirm the series on the drawing before drilling, and confirm against the governing edition of the standard. Both series share the ASME B16.5 rating tables, so rating does not change with diameter.
AWWA C207 covers carbon steel flanges from 4 in to 144 in in Classes B, D, E and F. AWWA C228 covers stainless steel flanges from 2 in to 72 in in 304L or 316L, in Classes SA, SB, SD, SE and SF. Both are rated in psi at water-service temperatures.
Carbon steel classes run B 86 psi, D 175 psi (150 psi at 14 in and larger), E 275 psi and F 300 psi. Stainless adds Class SA at 50 psi below Class SB and otherwise mirrors the same ratings with an S prefix. These suit large campus mains where diameter is large and pressure low.
ASME B16.5 flanges for cooling water cover NPS 1/2 through NPS 24 in Classes 150 to 2500. Forged carbon steel is ASTM A105, or ASTM A350 Gr. LF2 for low temperature; forged alloy and stainless grades are ASTM A182. Cooling pipework uses Class 150 and 300, and NPS 24 is the ceiling.
| Standard | Size range | Where it is used |
|---|---|---|
| ASME B16.5 | NPS 1/2 to NPS 24 | Most cooling pipework, Classes 150 and 300 |
| ASME B16.47 Series A | NPS 26 to NPS 60 | Large campus headers |
| ASME B16.47 Series B | NPS 26 to NPS 60 | Headers specified as compact flanges |
| AWWA C207 | 4 in to 144 in | Carbon steel campus mains, make-up water |
| AWWA C228 | 2 in to 72 in | Stainless mains, corrosive water service |
| EN 1092-1 | DN 10 upward | European and GCC drawings, PN 6 to PN 40 |
| IS 6392 | As per table | Indian project specifications |
EN 1092-1 flanges for cooling systems run PN 6 through PN 40 in Types 01, 02, 05 and 11, arriving with GCC and European drawings while the contractor works in ASME. PN and Class never share a joint, because the hole circles differ. Indian projects commonly pair IS 6392 with BS 4504 drilling.
Water chemistry selects the grade, and chloride level is the governing number.
| Grade | Specification | Where it suits | Chloride tolerance |
|---|---|---|---|
| SS 304 / 304L | ASTM A182 F304, F304L | Treated closed-loop chilled water | Low |
| SS 316 / 316L | ASTM A182 F316, F316L | Coolant-wetted service, facility water, TCS | Moderate |
| Duplex 2205 | UNS S31803, S32205 | Condenser water, raised chlorides | High |
| Super duplex 2507 | UNS S32750 | Coastal sites, concentrated circuits | Very high |
| Cupro-nickel 90/10 | Copper alloy | Seawater and brackish heat rejection | High in seawater |
| Titanium Grade 2 | Titanium | Seawater heat exchangers | Very high |
Grade 304L works on treated closed loops with a managed inhibitor package, and the low carbon variant limits carbide precipitation after welding. Molybdenum separates 316 from 304, raising chloride pitting resistance enough to make 316L the default for stainless steel flanges for data centers.
Open Compute Project guidance and coolant datasheets list stainless steel 304L, 316L or higher grades as acceptable wetted materials for PG25-class fluids, nominally 25% propylene glycol with high-purity water and an inhibitor package. SS 316L flanges for liquid cooling became the standard technology cooling system choice for chloride tolerance in make-up water, not the glycol, with testing to ASTM D8040. Stainless steel 316 flanges are the coolant-wetted starting point.
Condenser water concentrates as it evaporates, so duplex steel flanges for condenser water bring roughly double the yield strength and a higher PREN, allowing thinner large-diameter sections.
Dissimilar metal flange isolation completes the decision. Copper cold plates, aluminum components and stainless pipework share one path, and the circuit between them drives galvanic corrosion. A dielectric kit breaks it: isolating gasket, sleeve on every bolt, washers at both ends.
On Class 150 vs Class 300 flanges, specify Class 150 for standard chilled water and condenser water duty, and Class 300 on tall risers where static head plus pump head plus surge passes the rating. Rate against design pressure, not operating pressure.
On raised face vs flat face flange selection, raised face is the ASME B16.5 default at 1.6 mm (1/16 in). Flat face belongs wherever a steel flange bolts to a flat-faced cast iron pump or valve. That is a recurring field error in HVAC pipework, and it persists because the parts fit: ASME B16.1 cast iron Class 125 drilling matches Class 150 steel, so the raised face acts as a fulcrum against a brittle casting. ASME B31.1 gives one answer with two parts: the raised face on the steel flange is machined off, and a full-face gasket is fitted. Specifying a flat-face steel companion flange from the start achieves the same thing without machining, but the full-face gasket is required either way.
Liquid cooling pipework splits the water three ways. The condenser water system rejects heat outdoors, the facility water system feeds the hall, and the technology cooling system runs inside the coolant distribution unit out to the cold plates. The CDU controls that loop's pressure, temperature, flow and filtration, holding the supply above dew point. CDU flange connections there are commissioned, flushed and reopened repeatedly.
| Cooling loop | Typical line size | Usual grade |
|---|---|---|
| Chilled water header and risers | 200 to 900 NB | Carbon steel or SS 304L |
| Chilled water branch to CRAH | 50 to 150 NB | SS 304L |
| Condenser water and cooling tower | 150 to 600 NB | SS 316L or duplex 2205 |
| Facility water branch to CDU | 50 to 200 NB | SS 316L |
| TCS inside the CDU skid | 25 to 100 NB | SS 316L |
| Make-up water and drain lines | 15 to 50 NB | SS 304L or SS 316L |
Chilled water pipe flanges on the mains are the largest on site, and cooling tower pipe flanges on open circuits are where stainless earns its cost. Roughly 90% of a GB300 NVL72 rack's heat goes to liquid and about 10% leaves by air, keeping CRAH coil flange connections in the design. Liquid cooling manifold flanges sit at pumps and skid boundaries, and flanges for heat recovery loops change the gasket and movement allowance.
Rack power drives the connection count. Air cooling handles roughly 30 to 40 kW per rack, and direct-to-chip liquid cooling extends that to roughly 60 to 120 kW. NVIDIA puts the GB200 NVL72 at approximately 120 kW designed and the GB300 NVL72 at approximately 135 kW, with references up to 142 kW. ASHRAE TC 9.9 sets the facility water classes from W17 at 2 to 17 °C to W+ above 45 °C, with Uptime Institute observing convergence around 32 °C.
On flanged vs grooved pipe joints, grooved couplings install roughly three times faster than flanged joints and five times faster than welded joints. Against that, a flanged joint cannot be inspected without pressurizing the system, while a weld can be radiographed beforehand.
EPDM covers the full facility water and technology cooling range, which stays inside its roughly 110 °C continuous limit. Heat recovery circuits running hotter, or joints with heavy thermal cycling, move to spiral wound. PTFE suits chemical cleaning.
Match bolting to the flange: ASTM A193 Grade B8 studs with A194 Grade 8 nuts for austenitic stainless. The flange bolt tightening sequence runs in four passes:
Over-torquing crushes the gasket, and joints relax through the first thermal cycles, so a re-torque belongs in the handover plan.
Specifying 316L is wasted money if the weld is left scaled. Back-purge with argon and control heat input, because heat tint and free iron are where pitting starts once coolant is in the loop. ASTM A380 covers cleaning, descaling and passivation of stainless parts, and ASTM A967 covers passivation and its verification. Shed particles block cold plate microchannels, and flanged joints are the flush access points.
For flange leak prevention in data centers, Open Compute Project guidance recommends leak detection on threaded, flanged, crimped and fused connections. Flange insulation for chilled water uses removable jackets holding the vapor barrier, while expansion joints absorb nozzle load on cooling equipment flanges.
An EN 10204 3.1 certificate for flanges is the minimum on a data center order, carrying heat number, chemical analysis and mechanical properties. A 3.2 adds third-party endorsement, and dimensional inspection, hydrostatic testing, PMI and IGC testing to ASTM A262 go onto the ITP. MSS SP-25 covers marking, and stainless is packed away from carbon steel because iron from strapping seeds pitting later.
A complete flange specification checklist line reads: ASME B16.47 Series A, 750 NB, Class 150, weld neck, raised face, bore to Sch 10S, ASTM A182 F316L, EPDM ring gasket, EN 10204 3.1 with PMI.
We manufacture to ASME B16.5, ASME B16.47 Series A and B, AWWA C207 and C228, EN 1092-1, DIN and IS 6392, in ASTM A182 F304L, F316L, F321, F51 and A350 LF2. Seawater service moves to Monel 400 flanges, Inconel 625 or titanium Grade 2.
Send the specification and we will quote your flanges for data center cooling systems against it.
Weld neck flanges carry main headers, risers and pump discharge. The tapered hub transfers bending stress into the pipe wall, giving the best fatigue and thermal-cycling performance of any type. Above NPS 24 it is ordered to ASME B16.47.
Yes. Open Compute Project guidance and coolant datasheets list 304L, 316L or higher grades as acceptable wetted materials for PG25-class propylene glycol fluids. The preference tracks chloride tolerance in make-up water, not the glycol.
flanges for data center cooling systems, data center chilled water flanges, weld neck flanges for chilled water, slip-on flanges for cooling water lines, blind flanges for tap-off points, lap joint flanges with stub ends, ss 316l flanges for liquid cooling, stainless steel flanges for data centers, duplex steel flanges for condenser water, super duplex 2507 flanges for cooling towers, asme b16.47 series a flanges for chilled water headers, asme b16.47 series b large diameter flanges, awwa c207 flanges for campus mains, awwa c228 stainless steel flanges, en 1092-1 flanges for cooling systems, is 6392 flanges supplier in india, asme b16.5 class 150 flanges for cooling water, class 150 vs class 300 flanges, raised face vs flat face flange, flat face flanges for cast iron pumps, cdu flange connections, coolant distribution unit flanges, facility water system flanges, technology cooling system flanges, liquid cooling manifold flanges, crah coil flange connections, cooling tower pipe flanges, chilled water pipe flanges, flanges for heat recovery loops, flange adaptor for grooved piping, flanged vs grooved pipe joints, dielectric flange isolation kit, galvanic corrosion flange isolation, epdm gasket for chilled water flanges, flange bolt tightening sequence, flange insulation for chilled water, flange leak prevention in data centers, pg25 coolant compatible flanges, en 10204 3.1 certificate for flanges, large diameter flanges manufacturer in india, data center cooling flanges supplier in mumbai, data center flanges exporter.
| Bengaluru | Mumbai | Chennai | Hyderabad | Kolkata | Pune |
| New Delhi | Ahmedabad | Jaipur | Surat | Salem | Gandhinagar |
| Bhiwandi | Tiruppur | Sivakasi | Jamnagar | Thiruvananthapuram | Rajahmundry |
| Bhubaneswar | Vijaywada | Firozabad | Bokaro Steel City | Rajkot | Bharuch |
| Panna | Raipur | Cochin | Ludhiana | Panipat | Durgapur |
| Peenya | Pimpri-Chinchwad | Channapatna | Kharagpur | Nashik | Bareilly |
| Varanasi | Haldia | Rourkela | Bangalore | Moradabad | Indore |
| Visakhapatnam | Trivandrum | Pithampur | Dibrugarh | Angul | Gwalior |
| Coimbatore | Kannur | Nagpur | Vadodara | Rudrapur | Noida |
| Agra | Bhagalpur | Jamshedpur | Bhilai | Lucknow | Kanpur |
| Thane | Bhopal | Sri City | Bareilly | Hosdurg | Pithampur |